TCP-3N, TCP-3N2 - 3 phase monitoring relay (phase to neutral measurement)

-

for 3-wire and 4-wire 3-phase supplies

-

3 phase monitoring relay for
3x230/400V

-

monitors phase sequence

-

detects phase failure with
regenerated voltage present

-

measures phase to phase voltage
(adjustable from 110V to 440V)

-

detects neutral connection
(selectable by a DIP-switch)

-

monitors asymmetry (adjustable from
5% to 30%, selectable by DIP-switch)

-

22.5 or 45mm DIN rail mount housing